July 14, 2020
Definition of D001 Hazardous Waste Modernized
On July 7, 2020, EPA finalized an update to the RCRA characteristic of ignitability found in §261.21. [85 FR 40594] While not a major overhaul of the definition of a D001 waste, the final rule addresses four aspects of how to make such a hazardous waste determination by:
- Updating the SW–846 test methods for measuring the flash point of a liquid,
- Codifying existing guidance on the definition of “aqueous” as it pertains to the alcohol-content exclusion,
- Updating the cross-references to DOT hazardous materials regulations, and
- Allowing the use of non-mercury thermometers for several SW–846 test methods.
The final rule is very similar to the 2019 proposed rule [84 FR 12539] with one exception—it does not codify existing guidance on sampling multiphase wastes. However, the preamble to the final rule does provide extensive guidance on this topic. The preamble also details EPA’s latest position on the use of the pressure filtration technique specified in SW–846 Method 1311 for assessing the presence of an ignitable liquid versus using the paint filter liquids test (Method 9095).
Updating Flash Point Test Methods
SW–846 Methods 1010A and 1020B (Pensky-Martens and Setaflash flash point test methods, respectively) are updated to 1010B and 1020C. The update allows for the use of newer ASTM standards (D8175-18 and D8174-18, respectively), while retaining the older ASTM standards (D93-79 or D93-80 and D3278-78). Thus, between Methods 1010B and 1020C, there are now five test methods that can be used for measuring flash point to determine ignitability of liquids. According to EPA, “generators are not required to use all of the ASTM standards specified in EPA Methods 1010B and 1020C when making a hazardous waste determination on a specific waste.... [T]he generator should use the test method most appropriate for their waste based on knowledge of the waste.” [85 FR 40598] While the older standards represented the best practices and technologies in 1980, scientific and technological advances have made these methods outdated. The newer methods allow for improved electric-spark ignition devices, newer heating elements, and the use of non-mercury thermometers. This change does not impact how a generator will make a D001 characterization, but it will affect how an analytical testing lab performs its tests.
Codifying “Aqueous” Guidance in the Alcohol-Content Exclusion
Section 261.21(a)(1) contains an exclusion for aqueous wastes containing less than 24% alcohol. The final rule revised this exclusion by defining aqueous as “at least 50 percent water by weight.” EPA uses alcoholic beverages and aqueous latex paints as examples of how this exclusion could apply. These materials exhibit low flash points due to their alcohol content but do not sustain combustion because of their high water content. If a waste is similar in nature to one of these materials, it could be an indicator the waste is eligible for the exclusion. Although EPA did not finalize any other changes to the alcohol-content exclusion other than as noted above, the agency stated “a generator should consider the regulatory language itself as well as guidance that the agency has provided in the past.” For example, previous agency guidance in RO 13548 noting that an ignitable waste containing 77% water, 13% alcohol, and 10% non-alcohol liquid is eligible for the exclusion is still valid. [85 FR 40600] Though not codified, the agency also reiterated that the exclusion extends to wastes containing non-ethanol alcohols.
Updating DOT Cross-References
Sections 261.21(a)(3) and (4) define certain ignitable compressed gases and oxidizers, respectively, as D001 wastes based on language in the DOT regulations. The final rule removes obsolete DOT references and replaces them with current citations. Ignitable compressed gases [see §261.21(a)(3)(ii)(A)] are now identified using the current Division 2.1 flammable gas language in 49 CFR 173.115(a), while ignitable aerosol wastes will be designated as D001 per §261.21(a)(3)(ii)(B) if they meet the criteria in 49 CFR 173.115(l). One way to determine if you have one of these wastes is by looking at its DOT hazardous materials hazard class/division. If the waste you are shipping down the road is a DOT Division 2.1 flammable compressed gas, then it is a D001 ignitable compressed gas. The definition of an oxidizer as a D001 ignitable waste now correctly excludes DOT Division 1.1, 1.2, and 1.3 explosives. [§261.21(a)(4)(i)(A)] If the waste you are shipping down the road is a DOT hazard class 5.1 oxidizer or 5.2 organic peroxide, then it is a D001 oxidizer. In this final rule, Note 4 at the end of §261.21, which said that an organic peroxide is a type of oxidizer, was deleted. As a result, it is less clear in the regulations that organic peroxides are D001 when disposed. Additional clarification from EPA would be helpful.
Allowing the Use of Non-Mercury Thermometers
Numerous test methods, including the old flash point test methods, require the use of mercury thermometers. As part of its strategy for phasing out the use of mercury thermometers due to environmental, health, and safety concerns, EPA has modified SW–846 air sampling and stack emissions Methods 0010, 0011, 0020, 0023A, and 0051, as well as flash point Methods 1010B and 1020C, to allow the use of non-mercury thermometers. The final rule incorporated these test method revisions into §260.11 and Part 261, Appendix IX as appropriate.
Evaluating Multiphase Wastes
Section 262.11(a) states that a hazardous waste determination must be made at the point of generation and at any time in the course of its management that the waste has, or may have, changed its properties in a way that may impact its classification under RCRA. EPA’s long-standing sampling guidance states that for multiphase wastes, a sample should be separated into phases and each individual phase analyzed appropriately for the characteristic of ignitability. [RO 13759, 14834] Although proposed, the final rule did not codify this concept. Instead, the rule preamble [85 FR 40600–3] provided considerable discussion on how to make an ignitability characteristic determination for multiphase wastes, as summarized below:
- “When determining whether a waste contains multiple phases, the generator should consider the waste’s physical properties during its likely management. For example, if a waste is generated as one phase but based on the generator’s knowledge of the waste is likely to separate from one to two or more liquid phases during management (e.g., while stored or during transport), the generator is ultimately responsible for identifying the characteristics of the waste at the point of generation and also through the normal management of the waste. Alternatively, some wastes would not normally separate into multiple phases during management. In these cases, a generator might not find it necessary to take measures to separate the waste even if the waste could separate under certain conditions (e.g., changes in temperature, pressure, or composition) provided these conditions are unlikely to occur during normal management of the waste.”
- “In some limited situations, a waste may present as a liquid in nature but not pass through a paint filter due to viscosity or due to oversized particulates preventing flow through pores. In these situations, the agency recommends that the generator consider the possibility to decant, pipette, or use other physical means to collect a sample. Additionally, a generator would also be required to consider the identification of ignitable non-liquids under §261.21(a)(2) when materials are not determined to be a liquid via the paint filter liquids test.”
- “A generator of a waste should consider the individual liquid phases of a multiple phase waste under the criteria in 40 CFR 261.21(a)(1) and non-liquid phases of a multiple phase waste under the criteria of 40 CFR 261.21(a)(2) when those liquid or solid phases are representative samples of the waste as a whole.... Generators of multiple phases wastes where either phase is identified as exhibiting the characteristic of ignitability would be required to manage the entire waste as hazardous waste.”
- The agency discussed the applicability of Section 2.3.1.5 in Chapter 2 of SW–846 for sampling multiphase wastes, but concluded: “EPA believes that the sampling approaches outlined in Section 2.3.1.5, while providing useful guidance in certain circumstances, have limitations, as described. Ultimately, the sampling approach should be designed to obtain a representative sample of a waste or to provide additional knowledge of the waste when an individual sample does not wholly represent the hazards of a waste.”
Pressure Filtration Technique vs. Paint Filter Liquids Test
In previous guidance, EPA had noted that the pressure filtration technique specified in Method 1311 was the definitive procedure for determining if a waste contains a liquid. [January 13, 1995; 60 FR 3092] And the agency had website guidance (since deleted) noting that if the paint filter liquids test does not produce free liquid, the generator must use the pressure filtration test. In the preamble to the July 2020 rule, EPA appears to have backed away from its previous guidance, opening the door for the use of the more-common paint filter liquids test for determining the presence of a liquid when making an ignitability determination:
- “Therefore, a generator should consider their waste to be a multiple phase waste if at any time during the generation or likely management of the waste, a portion is determined by the generator to meet the definition of a liquid (e.g., as determined visually, by the paint filter liquids test, or through generator knowledge) and also has another phase consisting of a solid or a liquid.” [85 FR 40601]
- “Currently, generators may rely on the paint filter liquids test if they are separating a liquid from a solid for subsequent analysis.... [F]or most wastes that are not readily apparent to be a liquid through observation, the agency believes the paint filter liquids test is an appropriate analysis.” [85 FR 40603]
- EPA has not completely abandoned the use of the pressure filtration technique when determining the presence of a liquid phase: “The agency would also encourage the use of other tests such as the pressure filtration procedure within SW–846 Method 1311 if the generator determines the liquid resulting from pressure filtration more accurately represents their waste.” [85 FR 40601]
Effective Date and State Adoption
The rule is effective in Alaska and Iowa on September 8, 2020. The final rule is promulgated under the base RCRA program, meaning the changes do not take effect in RCRA-authorized states (all states other than Alaska and Iowa) until the states adopt them. Moreover, the revisions to the test methods are considered to be neither more nor less stringent than the existing regulations; thus, authorized states may, but are not required to, adopt these changes. [85 FR 40605]
©2020-2024 McCoy and Associates, Inc. All rights reserved.
McCoy and Associates has provided in-depth information to assist environmental professionals with complex compliance issues since 1982. Our seminars and publications are widely trusted by environmental professionals for their consistent quality, clarity, and comprehensiveness.
Disclaimer
Considerable care has been exercised in preparing this document; however, McCoy and Associates, Inc. makes no representation, warranty, or guarantee in connection with the publication of this information. McCoy and Associates, Inc. expressly disclaims any liability or responsibility for loss or damage resulting from its use or for the violation of any federal, state, or municipal law or regulation with which this information may conflict. McCoy and Associates, Inc. does not undertake any duty to ensure the continued accuracy of this information.
This document addresses issues of a general nature related to the federal environmental regulations. Persons evaluating specific circumstances dealing with the environmental regulations should review state and local laws and regulations, which may be more stringent than federal requirements. In addition, the assistance of a qualified professional should be enlisted to address any site-specific circumstances.